HOW
IT WORKS
Room temperature control in cooling is achieved
from a small amount of supply air which passes through an orifice
in the diffusion disc. The thermal control actuator senses the
air induced past it and varies the position of the diffusion disc
(immediately above it). The discharge opening is varied and results
in the varying of the supply air volume for cooling.
OPERATION
The SC “Smart” diffuser
is a single function device. It is powered by a single thermostatic
actuator to provide VAV room temperature control for cooling. As
room temperature increases above its set-point thermal actuator #
3 will sense and respond to the induced room air temperature. The
thermal actuator will react to the warming room temperature by extending
an internal piston allowing the diffusion disc to open. The increased
diffusion area allows more cool supply air to be delivered into the
room. As the room temperature decreases the opening of the diffusion
disc is reduced until the room temperature reaches the desired set-point.
When applied to interior spaces, or hot zones such as those created
by the excess heat from computers and office equipment, individual
VAV cooling provides the ultimate in room temperature control when
the supply air is cool.
FACE PANEL REMOVAL
The
solid face panel is held in place by four spring clips.
To remove the face panel for room temperature adjustments, approach
panel from the induction trough side (the rectangle opening) reach
above the panel on both sides with your forefingers until you are able
to place your forefingers behind the spring clips. Using your thumbs
on the front edge of the panel push
the panel back or away from you while pulling the spring
clips forward or toward you with your forefingers. Lower the panel
and pull forward to disconnect the panel from the rear spring clips.
When reattaching face panel the induction trough must be positioned
directly opposite of induction wing.
TEMPERATURE
ADJUST
Factory set-point approximately 74 degrees. For cooler room temperature,
turn room actuator clockwise. For warmer room temperature,
turn room actuator counter-clockwise. Determine room temperature
set-point by aligning end of the actuator with the indicators on
the temperature scale. Each full rotation or each indicator on the
temperature scale equals plus or minus 2 degrees. For 74 degree factory
set-point, turn actuator clockwise until stop, then turn counter-clockwise
3 full turns.